AROYA by Addium · Device Health · Curaleaf NY (facility 4412) · 2026-06-10

Curaleaf NY · Device Health & Data Continuity

Mesh backbone telemetry (48h) + 14-day per-room data-continuity audit (2026-05-27 → 2026-06-10).

Method & honesty note: per-device radio telemetry was sampled for the mesh backbone (gateways and sinks PoE-powered; the H340-series repeaters battery-powered, like the nodes); node/sensor-level status is inferred from data continuity in the 14-day room readings (the SPA device-status endpoint was unavailable this run). Climate (h421-class) devices never emit device-level radio series via this API — that is an API artifact, not an offline device. Gateways likewise emit no device-level series via this endpoint — gateway health is inferred from facility-wide data flow (all 27 rooms delivered data through the window ⇒ the gateway path is functional). Nodes, TEROS sensors and the H340-series repeaters are battery-powered; gateways, sinks and legacy H11x repeaters are PoE.
Fleet size
754
Repeaters/sinks silent (48h)
5 / 22
Rooms needing review
3 / 27
Rooms ≥90% data coverage (14d)
27 / 27

Fleet inventory

ModelCountRetired
Node (battery)3200
TEROS (battery)3200
Climate (PoE)440
EE894 CO2 (PoE)440
Mesh Repeater (H340 = battery; legacy H11x = PoE)180
Gateway (PoE)40
Sink (PoE)40

Mesh backbone — gateways & sinks (PoE), H340 repeaters (battery)

SerialModelRoomStatus (48h)RSSILinkTravelLast seen (UTC)
H2100005530gateway18552no device-series via API (artifact — not offline)
H2110001126gateway16415no device-series via API (artifact — not offline)
H2110001288gateway16423no device-series via API (artifact — not offline)
H2200001024gatewayno device-series via API (artifact — not offline)
H3400002030repeater16421reporting-55 dBm99%0 ms2026-06-10 12:57
H3400002031repeater18540reporting-56 dBm96%31 ms2026-06-10 13:00
H3400002032repeater16426reporting-52 dBm99%0 ms2026-06-10 12:57
H3400002033repeater16425reporting-46 dBm99%0 ms2026-06-10 12:57
H3400002038repeater16550reporting-74 dBm90%0 ms2026-06-10 12:57
H3400002039repeater16415reporting-47 dBm93%44 ms2026-06-10 13:00
H3400002040repeater16414reporting-75 dBm89%0 ms2026-06-10 12:57
H3400002703repeater18535reporting-83 dBm75%6 ms2026-06-10 12:57
H3400002738repeater18542reporting-68 dBm82%42 ms2026-06-10 13:00
H3400002739repeater16419reporting-57 dBm100%0 ms2026-06-10 12:57
H3400002740repeater18533reporting-81 dBm83%9 ms2026-06-10 12:57
H3400003057repeaterno telemetry 48h
H3400003058repeater18543reporting-63 dBm86%48 ms2026-06-10 13:00
H3400003059repeaterno telemetry 48h
H3400003060repeaterno telemetry 48h
H3400003068repeaterno telemetry 48h
H3400003069repeater18534reporting-70 dBm98%8 ms2026-06-10 12:57
H3400003070repeater18544reporting-66 dBm90%48 ms2026-06-10 13:00
SINKH2100005530sinkreporting255 dBm100%2026-06-10 12:54
SINKH2110001126sinkno telemetry 48h
SINKH2110001288sinkreporting255 dBm100%2026-06-10 12:57
SINKH2200001024sinkreporting255 dBm100%2026-06-10 12:57
Repeater RSSI (48h mean)

Per-room data continuity (14 days)

Coverage = % of 336 hourly slots with at least one reading. "Weak series" are individual sensor streams under 90% coverage; flagged zones (pegged EC / dead VWC) point at specific substrate sensors needing a re-seat or replacement.

RoomCoverageSeriesWeak seriesWeakest streamsSensor flagsVerdict
NY F1492.3%250review
NY F1594.6%250review
NY F13100.0%250healthy
NY F17100.0%250healthy
NY F18100.0%250healthy
NY F19100.0%250healthy
NY F20100.0%250healthy
NY F21100.0%250healthy
NY F22100.0%250healthy
NY F23100.0%250healthy
NY F24100.0%250healthy
Veg 2100.0%280healthy
NY F1100.0%280healthy
NY F2100.0%280healthy
NY F3100.0%280healthy
NY F4100.0%280healthy
NY F5100.0%280healthy
NY F7100.0%280healthy
Mom 1100.0%280healthy
Mom 2100.0%280healthy
Mom 3100.0%250healthy
NY F16 Veg100.3%4010abs_hum zroom_16420 86.9%; air_temp zroom_16420 86.9%; co2 zroom_16420 86.9%; rel_hum zroom_16420 86.9%; vpd zroom_16420 86.9%; air_temp z16420 86.9%zone 75784: VWC dead (1.7% mean); zone 75790: VWC dead (2.5% mean)review
NY F8100.3%280healthy
NY F9100.3%280healthy
NY F10100.3%280healthy
NY F11100.3%280healthy
NY F12100.3%400healthy
Room data coverage % (14d)

Source: AROYA public_api /devices/ + /devices/<id>/chart/ (backbone, 48h) + stitched /rooms/<id>/chart/ (14d). Battery models: Node, TEROS, H340-series repeaters. Gateways, sinks, legacy H11x repeaters and Atmos are PoE. Contact: cian@addium.com · Cian Sullivan · Addium / AROYA