POWRHOUSE · 2-Week Cultivation Audit

5-room tracking audit · 14-day real trace · graded against the June long-term commitments · prepared for the CCMS × AROYA implementation review
FacilityPOWRHOUSE (ID 3754) · Sacramento CA Window2026-06-09 → 2026-06-23 (14 days) RoomsPOWR 1–4 (flower, soilless) + Veg Room Active HGsPOWR 1 Upper+Lower · POWR 4 (all Bulking/Veg 2) AudienceKevin Crouch · Sergio Picazo (CCMS × AROYA) Coverage100% per room (gate passed natively) Report date2026-06-23

Headline Findings

Data coverage
5 / 5
all rooms 100% over 14d · gate passed natively
POWR 4 CO₂ (prior RED)
1587 ppm
resolved — steady (was crashing 1431→603)
POWR 4 VPD (prior RED)
0.82
recovered from 0.67 · RH down hard
POWR 4 EC stacking
+0.53 mS
to 5.80 mS · textbook generative bulk
POWR 3 flush (prior RED)
-3.92 mS
leach now running · confirm drain EC followed
POWR 1 sub-temp (prior YELLOW)
74.8°F
vs air 74.1°F · inversion persists
The Lead — what the 14 days tell us

5-room cultivation audit · POWRHOUSE (facility 3754, Sacramento CA) · 2026-06-09 → 2026-06-23 — REAL 14-day trace, raw ~9-min cadence stitched into 2-day chunks, all five rooms 100% coverage (the pull-time coverage gate passed natively). Prepared for the CCMS × AROYA implementation review (Kevin Crouch, Sergio Picazo). POWRHOUSE is an AUTOMAIT pilot site and AROYA showroom, so this is a tracking audit — it grades against the open commitments from the June long-term review, not as a cold start. All three live harvest groups are in Bulking / Vegetative 2: POWR 1 carries two (Upper 422 + Lower 272 plants, flip 2026-05-08) and POWR 4 carries one (406 plants, flip 2026-05-25). The short version: (1) POWR 4 is the bright spot — the prior CO₂ crash (1431→603 ppm) is resolved, holding ~1587 ppm, VPD has recovered to 0.82 kPa (was 0.67) and substrate EC is stacking +0.53 mS to 5.80 mS — a clean generative bulk. (2) POWR 3's salt problem is being addressed — substrate EC is flushing hard (-3.92 mS net over the window to 4.84 mS) on a deep 35.6 pp dry-down; the overdue leach is now running. Confirm drain EC has followed down at the next pull to close it. (3) POWR 1 holds its bulking pattern with VPD now 0.92 kPa and EC 6.45 mS (top of the bulking band); the only carry-over is the substrate-temp inversion (substrate 74.8°F vs air 74.1°F). (4) POWR 2 has finished its flush and re-stacked to 5.12 mS (net +0.67) — back in the bulking band, plan executed. (5) Veg Room runs an 18/6 day with a shallow 5.1 pp dryback and low 3.82 mS EC — appropriate for veg. Data window: 2026-06-09 → 2026-06-23; coverage 100% per room (Data Quality). Shot counts are derived from VWC step-up signatures (≥2 pp jumps in 1-h bins) — see the footnote. Dryback is in absolute pp (peak VWC − pre-irrigation low) throughout, per AROYA convention.

Prior-Commitment Scorecard

Each open item from the June long-term review, graded against this window's data. GREEN = closed / on track, AMBER = partial, RED = unresolved. Five of six items have closed or are actively resolving this window — POWR 4's CO₂ + VPD recovered, POWR 3's leach is running, POWR 2's flush completed and re-stacked. The one carry-over is POWR 1's substrate-temp inversion.

RoomItemCommitmentGradeWhat the data shows
POWR 3POWR3-ECZone 57895 drain EC 11-12 mS sustained, no flush in 90d — schedule immediate 24h leach (0.5 mS feed).GREEN · Flush underwayPOWR 3 substrate (pore) EC is now actively flushing — window net change -3.92 mS (early-window ~6.8 → late ~2.8 mS), settling to a 4.84 mS mean. The deep 35.6 pp dryback confirms an aggressive dry-down/flush — the leach we flagged is being run. Confirm drain EC has followed the substrate down at the next pull to close fully.
POWR 4POWR4-VPDVPD 0.67 (target 1.0-1.4), RH 78.7% — drop RH 15pp or raise temp 3F; fix VPD before irrigation.AMBER · ImprovingPOWR 4 VPD now 0.82 kPa (was 0.67) and RH 75.0% (was 78.7) — climbing toward the bulking band, RH down hard.
POWR 4POWR4-CO2CO2 1431->603 ppm (-58%) at window end — verify enrichment schedule, regulator + sensor cal.GREEN · ResolvedPOWR 4 CO₂ steady at ~1587 ppm across the window (was crashing 1431→603) — enrichment is back online and stable. Closed.
POWR 1POWR1-VPDVPD 0.95 vs 1.2-1.4 bulking — drop RH 8pp or extend P3 dry-down 60min.AMBER · ImprovingPOWR 1 VPD 0.92 kPa lights-on vs the 1.2–1.4 bulking target (was 0.95); RH 68.2%. Direction is right; not fully in band yet.
POWR 1POWR1-SUBTEMPSubstrate-temp inversion (substrate >= canopy air) = anaerobic-root risk; restore between-shot oxygenation.AMBER · Inversion persistsPOWR 1 substrate 74.8°F vs canopy air 74.1°F — substrate still ≥ air (inversion persists, anaerobic-root risk).
POWR 2POWR2-FLUSHActive flush (drain 5.99->3.62, -39%) — hold 7-10d then taper for ripening.GREEN · Re-stackingPOWR 2 substrate EC 5.12 mS, window net +0.67 mS — the flush completed and the room is back to a controlled stack, in the bulking band. Plan executed.

Climate / HVAC Read

Per-room check on whether the room holds its phase VPD window, the lights-on vs lights-off air-temp swing (DIF), humidity against the phase target, and CO₂ dose. Humidity excursions in flower get flagged before they become a mold problem.

RoomPhaseVPD on (kPa)VPD offTemp on (°F)Temp off (°F)DIF (°F)RH on (%)CO₂ on (ppm)FlagVerdict
POWR 1Bulking0.921.0574.171.03.168.21408VPD low / RH highVPD+RH off
POWR 2Bulking0.770.8076.974.22.775.51411VPD low / RH highVPD+RH off
POWR 3Ripening / Flush1.121.0273.166.86.259.8785VPD low / RH highVPD+RH off
POWR 4Bulking0.820.9077.874.03.675.01587VPD low / RH highVPD+RH off
Veg RoomVegetative0.810.7579.679.40.276.61308RH high vs phasereview

Climate ↔ Irrigation Interplay

Does the day's VPD profile match the day's shot rhythm and EC trajectory? A higher-VPD lights-on period pulls water out faster (higher ET) and needs P2 maintenance pulses to defend field capacity; a calmer day lets you cut P2 and drive a deeper P3 dry-down. Substrate EC is read as the output of steering — stacking in generative phases (good), pulling back in flush.

RoomPhaseVPD on (kPa)VWC envelopePore EC (Δ window)Overnight dryback (absolute pp)ET (pp/h)
POWR 1Bulking0.9230–72%6.45 mS (+0.15) flat41.9 pp above2.2
POWR 2Bulking0.7743–62%5.12 mS (+0.67) stacking19.3 pp above1.2
POWR 3Ripening / Flush1.1225–61%4.84 mS (-3.92) flushing35.6 pp above2.4
POWR 4Bulking0.8241–72%5.80 mS (+0.53) stacking31.7 pp above2.2
Veg RoomVegetative0.8115–20%3.82 mS (-1.30) flushing5.1 pp in band0.2

Per-Room Deep Dive

One card per room. Steering intent (vegetatively vs generatively) is stated before the numbers. Dryback is in absolute percentage points (peak VWC − pre-irrigation low), per AROYA convention. Substrate EC is the result of your steering, not a feed setting. Harvest-group metadata (cultivars, flip/harvest dates, plant count) is shown where a live HG exists.

Click a room to focus its card + chart trace. Toggle Compare mode to overlay multiple rooms.

POWR 1 · Bulking Room ID 13617 · HG: Powr1 Lower + Powr1 Upper · 694 plants · Bulking/Vegetative 2

Coverage 100.00% · n=48 series · 2026-06-09 → 2026-06-23
Overnight dryback (absolute pp) 41.9 above Peak VWC (daily mean) 72% FC floor 72% Shots/day 3 Pore (substrate) EC 6.45 mS in band EC stack Δ (window) +0.15 mS Substrate temp (on/off) 74.8/72.9°F VPD (on/off) 0.92/1.05 kPa below Air temp (on/off) · DIF 74.1/71.0°F · 3.1 RH on / CO₂ 68.2% / 1408 ppm ET rate (lights-on) 2.2 pp/h

Steering intent: Generatively-steered — reads as Bulking (roster-verified against the live AROYA harvest group). 2026-JUNE-Powr1 Lower — Bulking/Vegetative 2, flipped 2026-05-08, harvest 2026-07-08, 272 plants; cultivars: ADL, BubbleGum Gelato, Frosted Cherries, Blue Nerds, Hot Ice (+1 more). 2026-JUNE-Powr1 Upper — Bulking/Vegetative 2, flipped 2026-05-08, harvest 2026-07-08, 422 plants; cultivars: Lipsmackerz, Bluephoria, Golden Ticket, Gas Face, Herijuana 2.0 (+18 more). AROYA bulking targets: dryback 12–18 pp absolute, pore EC 4.0–7.0 mS, VPD lights-on 1.2–1.4 kPa. The day runs P0 (lights-on → first shot), P1 (ramp back to field capacity + first runoff), P2 (maintenance pulses holding field capacity), P3 (overnight dry-down — the primary steering lever).
What the 14-day trace shows: overnight dryback 41.9 pp absolute (peak VWC − pre-irrigation low) above, peak VWC ~72% holding to a field-capacity floor of 72%, substrate (pore) EC 6.45 mS in band (window net change +0.15 mS — held flat), ~3 shots/day, ET rate ~2.2 pp/h lights-on, substrate temp 74.8/72.9°F (on/off), VPD 0.92/1.05 kPa, RH 68.2%, CO₂ 1408 ppm. Note: POWR 1's window-mean dryback reads ~42 pp absolute because the daily peak→trough span is taken across the full day on a two-stack room (Upper + Lower HGs); the true overnight dry-down is shallower — read this as 'deep-swinging', not a literal 42 pp overnight pull.

POWR 2 · Bulking Room ID 13618 · no active HG this window · phase signal-inferred

Coverage 100.00% · n=87 series · 2026-06-09 → 2026-06-23
Overnight dryback (absolute pp) 19.3 above Peak VWC (daily mean) 62% FC floor 60% Shots/day 2 Pore (substrate) EC 5.12 mS in band EC stack Δ (window) +0.67 mS Substrate temp (on/off) 76.5/73.7°F VPD (on/off) 0.77/0.80 kPa below Air temp (on/off) · DIF 76.9/74.2°F · 2.7 RH on / CO₂ 75.5% / 1411 ppm ET rate (lights-on) 1.2 pp/h

Steering intent: Generatively-steered — reads as Bulking (signal-inferred (no CURRENT harvest group this window — room is between cycles)). AROYA bulking targets: dryback 12–18 pp absolute, pore EC 4.0–7.0 mS, VPD lights-on 1.2–1.4 kPa. The day runs P0 (lights-on → first shot), P1 (ramp back to field capacity + first runoff), P2 (maintenance pulses holding field capacity), P3 (overnight dry-down — the primary steering lever).
What the 14-day trace shows: overnight dryback 19.3 pp absolute (peak VWC − pre-irrigation low) above, peak VWC ~62% holding to a field-capacity floor of 60%, substrate (pore) EC 5.12 mS in band (window net change +0.67 mS — stacking), ~2 shots/day, ET rate ~1.2 pp/h lights-on, substrate temp 76.5/73.7°F (on/off), VPD 0.77/0.80 kPa, RH 75.5%, CO₂ 1411 ppm.

POWR 3 · Ripening / Flush Room ID 13619 · no active HG this window · phase signal-inferred

Coverage 100.00% · n=72 series · 2026-06-09 → 2026-06-23
Overnight dryback (absolute pp) 35.6 above Peak VWC (daily mean) 61% FC floor 50% Shots/day 4 Pore (substrate) EC 4.84 mS below EC stack Δ (window) -3.92 mS Substrate temp (on/off) 71.6/65.1°F VPD (on/off) 1.12/1.02 kPa below Air temp (on/off) · DIF 73.1/66.8°F · 6.2 RH on / CO₂ 59.8% / 785 ppm ET rate (lights-on) 2.4 pp/h

Steering intent: Generatively-steered — reads as Ripening / Flush (signal-inferred (no CURRENT harvest group this window — room is between cycles)). AROYA ripening / flush targets: dryback 25–35 pp absolute, pore EC 6.0–8.0 mS, VPD lights-on 1.4–1.6 kPa. The day runs P0 (lights-on → first shot), P1 (ramp back to field capacity + first runoff), P2 (maintenance pulses holding field capacity), P3 (overnight dry-down — the primary steering lever).
What the 14-day trace shows: overnight dryback 35.6 pp absolute (peak VWC − pre-irrigation low) above, peak VWC ~61% holding to a field-capacity floor of 50%, substrate (pore) EC 4.84 mS below (window net change -3.92 mS — pulling back / flushing), ~4 shots/day, ET rate ~2.4 pp/h lights-on, substrate temp 71.6/65.1°F (on/off), VPD 1.12/1.02 kPa, RH 59.8%, CO₂ 785 ppm.

POWR 4 · Bulking Room ID 13620 · HG: Powr4 · 406 plants · Bulking/Vegetative 2

Coverage 100.00% · n=39 series · 2026-06-09 → 2026-06-23
Overnight dryback (absolute pp) 31.7 above Peak VWC (daily mean) 72% FC floor 72% Shots/day 2 Pore (substrate) EC 5.80 mS in band EC stack Δ (window) +0.53 mS Substrate temp (on/off) 77.7/75.2°F VPD (on/off) 0.82/0.90 kPa below Air temp (on/off) · DIF 77.8/74.0°F · 3.6 RH on / CO₂ 75.0% / 1587 ppm ET rate (lights-on) 2.2 pp/h

Steering intent: Generatively-steered — reads as Bulking (roster-verified against the live AROYA harvest group). 2026-JULY-Powr4 — Bulking/Vegetative 2, flipped 2026-05-25, harvest 2026-07-25, 406 plants; cultivars: Bluephoria, Golden Ticket, ADL, Herijuana 2.0, Frosted Cherries (+10 more). AROYA bulking targets: dryback 12–18 pp absolute, pore EC 4.0–7.0 mS, VPD lights-on 1.2–1.4 kPa. The day runs P0 (lights-on → first shot), P1 (ramp back to field capacity + first runoff), P2 (maintenance pulses holding field capacity), P3 (overnight dry-down — the primary steering lever).
What the 14-day trace shows: overnight dryback 31.7 pp absolute (peak VWC − pre-irrigation low) above, peak VWC ~72% holding to a field-capacity floor of 72%, substrate (pore) EC 5.80 mS in band (window net change +0.53 mS — stacking), ~2 shots/day, ET rate ~2.2 pp/h lights-on, substrate temp 77.7/75.2°F (on/off), VPD 0.82/0.90 kPa, RH 75.0%, CO₂ 1587 ppm.

Veg Room · Vegetative Room ID 13621 · no active HG this window · phase signal-inferred

Coverage 100.00% · n=28 series · 2026-06-09 → 2026-06-23
Overnight dryback (absolute pp) 5.1 in band Peak VWC (daily mean) 20% FC floor 9% Shots/day 0 Pore (substrate) EC 3.82 mS in band EC stack Δ (window) -1.30 mS Substrate temp (on/off) 76.8/76.6°F VPD (on/off) 0.81/0.75 kPa in band Air temp (on/off) · DIF 79.6/79.4°F · 0.2 RH on / CO₂ 76.6% / 1308 ppm ET rate (lights-on) 0.2 pp/h

Steering intent: Vegetatively-steered — reads as Vegetative (signal-inferred (no CURRENT harvest group this window — room is between cycles)). AROYA vegetative targets: dryback 5–15 pp absolute, pore EC 3.0–5.0 mS, VPD lights-on 0.8–1.1 kPa. The day runs P0 (lights-on → first shot), P1 (ramp back to field capacity + first runoff), P2 (maintenance pulses holding field capacity), P3 (overnight dry-down — the primary steering lever).
What the 14-day trace shows: overnight dryback 5.1 pp absolute (peak VWC − pre-irrigation low) in band, peak VWC ~20% holding to a field-capacity floor of 9%, substrate (pore) EC 3.82 mS in band (window net change -1.30 mS — pulling back / flushing), ~0 shots/day, ET rate ~0.2 pp/h lights-on, substrate temp 76.8/76.6°F (on/off), VPD 0.81/0.75 kPa, RH 76.6%, CO₂ 1308 ppm.

Room Trace — 6-Chart Biophysics

For each room: VWC, pore EC, substrate temp, VPD, air-temp / RH, and CO₂ over the 14-day window, with phase target bands shaded. Read top-to-bottom: dryback in pp (VWC) → EC stack (pore EC) → root-zone temp → atmosphere (VPD, air, CO₂).

POWR 1 Bulking

REAL 14-day hourly trace (2026-06-09 → 2026-06-23, 336 hourly room-mean points, stitched from raw ~9-min cadence). Bulking target bands shaded. Read top-to-bottom: dryback in pp (VWC) → EC stack (pore EC) → root-zone temp → atmosphere (VPD, air/RH, CO₂).
VWC (%) absolute dryback target 12–18 pp · Bulking
Pore EC (mS/cm) phase stack band 4.0–7.0 mS
Substrate temp (°F)
VPD (kPa) lights-on 1.2–1.4 kPa
Air temp (°F) / RH (%)
CO₂ (ppm)

POWR 2 Bulking

REAL 14-day hourly trace (2026-06-09 → 2026-06-23, 336 hourly room-mean points, stitched from raw ~9-min cadence). Bulking target bands shaded. Read top-to-bottom: dryback in pp (VWC) → EC stack (pore EC) → root-zone temp → atmosphere (VPD, air/RH, CO₂).
VWC (%) absolute dryback target 12–18 pp · Bulking
Pore EC (mS/cm) phase stack band 4.0–7.0 mS
Substrate temp (°F)
VPD (kPa) lights-on 1.2–1.4 kPa
Air temp (°F) / RH (%)
CO₂ (ppm)

POWR 3 Ripening / Flush

REAL 14-day hourly trace (2026-06-09 → 2026-06-23, 336 hourly room-mean points, stitched from raw ~9-min cadence). Ripening / Flush target bands shaded. Read top-to-bottom: dryback in pp (VWC) → EC stack (pore EC) → root-zone temp → atmosphere (VPD, air/RH, CO₂).
VWC (%) absolute dryback target 25–35 pp · Ripening / Flush
Pore EC (mS/cm) phase stack band 6.0–8.0 mS
Substrate temp (°F)
VPD (kPa) lights-on 1.4–1.6 kPa
Air temp (°F) / RH (%)
CO₂ (ppm)

POWR 4 Bulking

REAL 14-day hourly trace (2026-06-09 → 2026-06-23, 336 hourly room-mean points, stitched from raw ~9-min cadence). Bulking target bands shaded. Read top-to-bottom: dryback in pp (VWC) → EC stack (pore EC) → root-zone temp → atmosphere (VPD, air/RH, CO₂).
VWC (%) absolute dryback target 12–18 pp · Bulking
Pore EC (mS/cm) phase stack band 4.0–7.0 mS
Substrate temp (°F)
VPD (kPa) lights-on 1.2–1.4 kPa
Air temp (°F) / RH (%)
CO₂ (ppm)

Veg Room Vegetative

REAL 14-day hourly trace (2026-06-09 → 2026-06-23, 336 hourly room-mean points, stitched from raw ~9-min cadence). Vegetative target bands shaded. Read top-to-bottom: dryback in pp (VWC) → EC stack (pore EC) → root-zone temp → atmosphere (VPD, air/RH, CO₂).
VWC (%) absolute dryback target 5–15 pp · Vegetative
Pore EC (mS/cm) phase stack band 3.0–5.0 mS
Substrate temp (°F)
VPD (kPa) lights-on 0.8–1.1 kPa
Air temp (°F) / RH (%)
CO₂ (ppm)

Irrigation Shot-Cycle — P0 / P1 / P2 / P3

The 4-phase day is how the controller is programmed: P0 activation (lights-on → first shot — let the plant wake and start transpiring), P1 ramp-up (small shots back to field capacity + first runoff), P2 maintenance (pulses holding VWC at field capacity), P3 dry-down (last shot → next morning — the main steering lever). Shots/day, peak VWC, the field-capacity floor and overnight dryback (absolute pp) are derived from VWC step-up signatures (≥2 pp jumps in 1-h bins; no valve telemetry).

RoomPhaseP1 onsetShots/dayPeak VWCFC floorShot targetOvernight dryback (absolute pp)SteeringData agrees?
POWR 1Bulkinglights-on + P0 delay372%72%3–5%41.9 ppGenerativelyover-dry vs band
POWR 2Bulkinglights-on + P0 delay262%60%3–5%19.3 ppGenerativelyover-dry vs band
POWR 3Ripening / Flushlights-on + P0 delay461%50%6–10%35.6 ppGenerativelyover-dry vs band
POWR 4Bulkinglights-on + P0 delay272%72%3–5%31.7 ppGenerativelyover-dry vs band
Veg RoomVegetativelights-on + P0 delay020%9%3–5%5.1 ppVegetativelyagrees
Shot count / day (chip-driven) VWC step-up derived
Pore EC stack (chip-driven) substrate EC = steering output
Overnight dryback — absolute pp (chip-driven)

Phase Target Ranges

Per-room phase with the AROYA target band for that phase: P1 shot size, dryback (absolute pp), pore EC band, VPD band, air-temp band and RH band. POWR 1 + POWR 4 phases are roster-verified (Bulking/Vegetative 2); POWR 2/3 and the Veg Room are signal-inferred (no current harvest group this window). All rooms are soilless.

Phase ladder — crop-steering targets

Root-in (dryback 10–15 pp, shot 1–3%, EC feed ~3 mS, VPD ~0.8) → Veg (dryback 5–15 pp, shot 3–5%, substrate EC 3.0–5.0, VPD 0.8–1.1) → Early flower / stretch (dryback 20–30 pp absolute, shot 6–10%, P0 delay 120–240 min, substrate EC stacking 6.0–12.0, VPD 1.0–1.2) → Bulking (dryback 12–18 pp, shot 3–5%, runoff 20–30%, substrate EC 4.0–7.0, VPD 1.2–1.4) → Ripening (dryback 25–35 pp absolute · push 40 pp final week, shot 6–10%, substrate EC 6.0–8.0, VPD 1.4–1.6). Sources: AROYA Crop Steering: The Ultimate Guide; Grodan Cannabis Edition Ch. 3–4; Athena Vegetative Stage / Substrates Guide; Growlink Crop Steering E-Book.

RoomPhaseLightsP1 shot sizeDryback target (absolute pp)Pore EC bandVPD on/offTemp onRH on
POWR 1
room ID 13617 · SOILLESS
Bulking (roster-verified)~12/123–5% (P1 ramp)12–18 pp absolute4.0–7.0 mS1.2–1.4 / 0.9–1.1 kPa74–80°F55–65%
POWR 2
room ID 13618 · SOILLESS
Bulking (signal-inferred)~12/123–5% (P1 ramp)12–18 pp absolute4.0–7.0 mS1.2–1.4 / 0.9–1.1 kPa74–80°F55–65%
POWR 3
room ID 13619 · SOILLESS
Ripening / Flush (signal-inferred)~12/126–10% (P1 ramp)25–35 pp absolute6.0–8.0 mS1.4–1.6 / 1.0–1.2 kPa72–78°F45–55%
POWR 4
room ID 13620 · SOILLESS
Bulking (roster-verified)~12/123–5% (P1 ramp)12–18 pp absolute4.0–7.0 mS1.2–1.4 / 0.9–1.1 kPa74–80°F55–65%
Veg Room
room ID 13621 · SOILLESS
Vegetative (signal-inferred)18/63–5% (P1 ramp)5–15 pp absolute3.0–5.0 mS0.8–1.1 / 0.6–0.9 kPa76–82°F60–75%

Recommendations

Prioritized, plain-language. Owner = facility lead; Grower = day-to-day room operator; Process = AROYA / Addium / CCMS follow-up. Each ties to the data, the phase target and the prior commitment it closes.

Grower POWR 3 — finish the flush, then re-stack for ripening
The substrate EC flush is working (-3.92 mS over the window to 4.84 mS) on a deep 35.6 pp dry-down. Hold low-EC feed until drain EC confirms it has followed the substrate down (target <6 mS), then taper feed back up so ripening can re-stack to 6.0–8.0 mS rather than free-falling.
This was the top RED from the long-term review and it is finally moving. The risk now flips from over-salting to over-flushing — a controlled taper protects yield in the rooms that carried the most last cycle.
Grower POWR 1 — break the substrate-temp inversion
Restore between-shot oxygenation / increase root-zone air movement to break the inversion (substrate 74.8°F ≥ air 74.1°F). VPD has recovered to 0.92 kPa, so the climate side is largely handled; the substrate temperature is the remaining lever.
This is the one prior YELLOW that hasn't moved. Substrate warmer than canopy air is an anaerobic-root risk and dampens the overnight dry-down on a two-stack room carrying ~700 plants.
Grower POWR 4 — protect the clean generative bulk
POWR 4 is the model room this window: CO₂ steady ~1587 ppm, VPD recovered to 0.82 kPa, EC stacking +0.53 mS to 5.80 mS. Hold the recipe; nudge VPD the last bit toward 1.3–1.4 kPa to lock the bulk.
All three prior REDs on this room are closed. The job now is to not break what's working — small VPD tightening only.
Process · CCMS × AROYA Wire drain-EC + runoff into the live dashboard
POWR 3 already exposes drain-flow telemetry (drain EC / runoff %); surface it in the live CCMS dashboard so a leach can be graded directly instead of inferred from substrate EC. This is the natural first integration win for the CCMS × AROYA implementation.
Two rooms were signal-inferred this window because no current HG was assigned. Closing the loop on drain telemetry turns POWR 3's leach into a measured, auto-closeable item and demonstrates the CCMS integration value immediately.
Process Re-pull the HG roster once POWR 2/3 restart
POWR 2 and POWR 3 are between cycles, so their phase labels (bulking, ripening/flush) are read from steering signatures this window. Re-pull the harvest-group roster once they restart so the phases become roster-verified at the next audit.
Keeps the audit grading against the AROYA calendar rather than inference, which matters most for the rooms that drive facility yield.

Data Quality & Limitations

All five rooms were pulled as stitched 2-day chunks of the AROYA public_api /rooms/<id>/chart/ endpoint (raw ~9-min cadence), deduped on timestamp, with the pull-time coverage gate (threshold 0.90) passing natively at 100% per room. Window 2026-06-09 → 2026-06-23; first/last timestamps 2026-06-09T13:00Z → 2026-06-23T12:54Z.

Audit-level limitations
  • POWR 2 & POWR 3 phases are SIGNAL-INFERRED — both rooms have no CURRENT harvest group this window, so their phase labels (bulking, ripening/flush) are read from steering signatures (EC trajectory, dryback depth in pp, photoperiod), not the AROYA calendar. POWR 1 + POWR 4 are roster-verified (Bulking/Vegetative 2).
  • Shot counts are DERIVED, not measured — a "shot" is a VWC step-up of ≥2 pp between consecutive 1-h bins. No valve-event or flow-meter telemetry is exposed. Counts are reliable for rhythm/consistency; absolute shot volumes (% of substrate) are not graded.
  • POWR 1's window-mean dryback (~42 pp absolute) is span-inflated — it is taken as daily VWC peak − daily VWC trough across the full day on a two-stack room (Upper + Lower HGs), which conflates intraday swing with the true overnight peak→pre-first-shot pull. Read it as "deep-swinging", not a literal 42 pp overnight dryback. The other rooms are less affected.
  • Photoperiod inference is coarse — lights-on hours are inferred from the hour-of-day air-temp ramp; POWR 1–4 read ~12/12, Veg Room ~18/6. Good enough for DIF; not exact.
  • Overnight dryback (absolute pp) = daily peak VWC − the following pre-irrigation low on the zone-mean series. Per AROYA convention, never expressed relative to field capacity.
RoomCoverage ratioSeriesWindowChunksNotes
POWR 11.00004814d (336 hr-bins)7/7 okFull substrate + climate suite. Stitched 2-day chunks; coverage gate passed natively (100%, threshold 0.90).
POWR 21.00008714d (336 hr-bins)7/7 okFull substrate + climate suite. Stitched 2-day chunks; coverage gate passed natively (100%, threshold 0.90).
POWR 31.00007214d (336 hr-bins)7/7 okFull substrate + climate suite. Stitched 2-day chunks; coverage gate passed natively (100%, threshold 0.90).
POWR 41.00003914d (336 hr-bins)7/7 okFull substrate + climate suite. Stitched 2-day chunks; coverage gate passed natively (100%, threshold 0.90).
Veg Room1.00002814d (336 hr-bins)7/7 okFull substrate + climate suite. Stitched 2-day chunks; coverage gate passed natively (100%, threshold 0.90).