2-Week Facility Audit

Zugatti · 14th street · Device Health

Operator pre-meeting audit. Window 2026-06-01 → 2026-06-15 (14 days).
FacilityZugatti: 14th street · ID 2704 OrgDUB BROS. MANAGEMENT LLC · ID 2076 Window2026-06-01 → 2026-06-15 Generated2026-06-15

Device Health · 2026-06-15

Rooms reporting
3 of 6 probed
F1/F2/F3 live; Veg dark
Worst offender
Veg (4837)
0 series for full window
Sensor faults
2
F1 pore_ec pinned 30.0; F3 zone 10277 intermittent (n=45)
Climate sensor gaps
Flower 3
Substrate OK, no room air/VPD/RH
Headline
The Veg room (4837) is fully sensor-dark — zero readings across the entire 2026-06-01→2026-06-15 window. That is the top device-health issue. Two secondary faults: Flower 1's room pore-EC channel is pinned at exactly 30.0 (a placeholder/fault, not a real reading), and Flower 3 has no room climate sensor reporting (only its TEROS substrate zones) with zone 10277 intermittent (n=45 vs 480 expected). Power note: Node + TEROS 12 and H340-series mesh repeaters are battery-powered; Climate One, Atmos 14, legacy H11x repeaters and gateway are PoE — a dark Veg room with no battery devices points at a gateway/mesh or PoE-power issue rather than dead node batteries.
RoomHardwareStatus / faultReading cadenceState
Flower 2 (4833)6 substrate zones + Climate One headVerified — air/VPD/RH + 6 TEROS zones reportingContinuous through 06-15active
Flower 1 (4832)6 substrate zones + Climate One headReporting but idle-room signature; pore_ec:room pinned at 30.0 (sensor placeholder/fault)Continuous; one EC channel faultedidle
Flower 3 (4834)6 substrate zones; NO room climate seriesSubstrate (TEROS) OK; room air/VPD/RH absent — Climate One/Atmos missing/offline. Zone 10277 only n=45 (intermittent).Substrate continuous; climate head silentactive (substrate)
Veg (4837)unknown0 series / 0 points for the full 14-day window — entire room offlineNo data in windowsensor-dark
Flower 4 (4835)unknownNot probed within budget; HG history ended 2025-03-18unprobed
Dry Room (4836)unknownNot probed (out of cultivation scope)unprobed

Per-series reading count vs expected (n, window)

Expected ≈480 readings/series across the window at hourly bins. Veg returns 0; Flower 1/2/3 substrate channels return ~480; Flower 3 zone 10277 returns only 45 (intermittent).

Method: device reliability derived from MCP reading-cadence + gap analysis (get_raw_data series presence and per-series n across the window). The SPA /devices/ endpoint (battery/RSSI/link) was not reachable unattended this run, so per-device battery/RSSI are not shown — this is a cadence-and-gap reliability view, flagged honestly. Repeater serials would be shown H-prefixed externally.

Cultivation linkage: these sensors feed the crop-steering phase model (P0 activation, P1 ramp-up, P2 maintenance, P3 dry-down) and overnight dryback (absolute pp). A sensor-dark room cannot be phase-steered — restoring the Veg-room mesh is a prerequisite for any P0–P3 steering or dryback measurement there.